Dakea Smoke Vent Energy Window for Sloped Roofs - KAS B1600
Online Only Item
This item is only available online and not instore. Please contact us if you require more information 01629 732988
Dakea Smoke Vent Energy Window for Sloped Roofs - KAS B1600
Features & Benefits
APPLICABLE
Window
- In common access areas of pitched roof buildings, such as stairwells, offices, etc.
- In roof pitch range of 15°-60°
- Suitable on all common roofing with proper flashing
Wind Deflector
- Warehouses, assembly plants
- For construction projects in which an aerodynamic opening area is required.
- Extra side element with foam for high profile roofing materials
FEATURES
- Complete smoke-ventilation system
- Smoke ventilation roof window (KAS) tested and certified according to EN 12101-2
- In case of fire opens to maximum position within 60 seconds
- Centre pivot wooden roof window
- Preinstalled opening motor
- Gas strut assisted opening
- Toughened outer glass
- Laminated internal safety glass
- Double gasket system between frame and sash
- Double Low-e coating
- Easy installation
- 10+10 year guarantee
- Optional wall switch available for comfort ventilation
- Optional rain sensor available for comfort ventilation
- Cannot be used for roof exit or escape purposes!
MATERIAL
Window
- Kiln-dried laminated pine wood
- Timber from FSC certified forests
- Fungicide protection
- Water based lacquer
Wind Deflector
- Steel
- Powder coated grey, RAL7043
COVER PARTS
- Aluminium, lacquered, grey colour (RAL 7043)
HINGE
- Pivot hinge
Technical Parameters (Pane)
| Construction | 33.2-10-3HS-10-4H |
| Thickness of glazing (mm) | 33 |
| Low E |
|
| Gas | Argon |
| Toughened | |
| Laminated | |
| Ug ( W/m2K ) | 0.81 |
| Total solar energy transmittance | 0.53 |
Technical Parameters (Window)
| Uw ( W/m2K ) | 1.1 |
| Water tightness | E1200 |
| Air permeability | Class 4 |
| Resistance to wind load | C4* |
| Sound reduction | 36 (-1,-3) dB |
* M8A, S8A, U8A: no performance data
Colour
| Natural wood (KAS B1600) |
Classification in Accordance with the Parameters of EN 12101-2 (KAS B1600)
| Reliability (Re) | Re 1000 + 10000 |
| Snow load (SL) | SL 1000** |
| Low Temperature (T) | T (-15) |
| Wind load (WL) | WL 3000*** |
| Heat Exposure (B) | B 300 |
** U8A size: SL 800, *** U8A size: WL 1500